Product Details
Article number: SK 3243.100
Product
description
Fan-and-filter
units with diagonal fan technology have superior pressure stability and ensure
a more constant air throughput. The diagonal direction of outflow ensures more
even heat dissipation from the enclosure.
Colour
RAL 7035
Supply
includes
Complete unit
ready to install, including chopped-fibre filter mat
Fan
Diagonal, 1~
capacitor motor
Air
throughput, unimpeded airflow (with chopped-fibre filter)
At 50
Hz: 540 m³/h
At 60 Hz: 590 m³/h
Air
throughput, unimpeded airflow (with pleated filter)
At 50
Hz: 625 m³/h
At 60 Hz: 716 m³/h
Air throughput
with outlet filter including chopped-fibre filter mat (quantity x order number)
1 x 3243200:
405/460 m³/h
2 x 3243200:
475/520 m³/h
Rated
operating voltage
230 V,
1~, 50 Hz/60 Hz
Power
consumption Pel
At 50
Hz: 70 W
At 60 Hz: 87 W
Rated current
max.
At 50
Hz: 0.37 A
At 60 Hz: 0.39 A
Dimensions
Width: 323
mm
Height: 323 mm
Mounting
cut-out
Cut-out
width: 292 mm
Cut-out height: 292 mm
Installation
depth
118.5 mm
IP protection
category to IEC 60 529
IP54 with
chopped-fibre filter/pleated filter
IP55 with
pleated filter and absorber mat
IP56 with
chopped-fibre filter/pleated filter and hose-proof hood
Protection
category NEMA
Type 12 with
chopped-fibre filter/pleated filter
Type 3, 3R, 4,
4X with chopped-fibre filter/pleated filter and hose-proof hood
Pre-fuse
Miniature
circuit-breaker/fuse: 4 A
Note
To increase
the air throughput, a pleated filter may optionally be used (see characteristic
curve). Suitable for use with fan-and-filter units, roof-mounted fans and
outlet filters.
With the
fan-and-filter unit 3237.XXX, electrical connection is made via two single
wires (length approx. 300 mm) on the unit, for all other fan-and-filter units,
a screwless spring terminal is used
Service life
of fans (L10, 40 °C)
At 50
Hz: 65,000 h
At 60 Hz: 61,000 h
Operating
temperature range
-30 °C...55 °C
Storage
temperature range
-30 °C...70 °C
Noise level
At 50
Hz: 59 dB(A)
At 60 Hz: 61 dB(A)
Packs of
1 pc(s).